Brand | Wone Store |
Model NO. | 10kV overhead insulated cable |
Rated voltage | 10kV |
Rated frequency | 50/60Hz |
Series | JKLYJ |
Product use
This product is suitable for transmission and distribution lines with AC rated voltage of 10kV and below, and is used to transmit power on overhead transmission lines.
Implementation standards
This product implements GB/T 14049-2008, Q/0900 TKD001-2022, Q/0900 TKD009-2017.
Characteristics of use
The maximum long-term temperature allowed for the conductor during normal operation of the cross-linked polyethylene insulated overhead cable is 90 °C, and the maximum temperature allowed for the cable conductor is 250 °C in the event of a short circuit (the maximum duration does not exceed 5s);
The minimum allowable laying temperature of the cable is not less than -20°C;
Bending requirements for overhead insulated cables:
The minimum bending radius of single-core cable is 20 (D+d) ±5%;
The minimum bending radius of multi-core cable is 15 (D+d) ±5%.
Note: D is the actual outer diameter of the cable, and d is the actual outer diameter of the cable conductor
Product model specifications
Product model
Model |
name |
JKYJ |
Copper-core XLPE insulated overhead cable |
JKTRYJ |
Soft copper core XLPE insulated overhead cable |
JKLYJ |
Aluminum-core cross-linked polyethylene insulated overhead cable |
JKLHYJ |
Aluminum alloy core XLPE insulated overhead cable |
JKLGYJ |
Steel core aluminum stranded core XLPE insulated overhead cable |
JKLYJ/Q |
Aluminum-core lightweight XLPE thin insulated aerial cable |
JKLHYJ/Q |
Aluminum alloy core lightweight XLPE thin insulated overhead cable |
Product specifications
Model |
Number of cores |
Nominal cross-section/mm2 |
JKYJ、JKLYJ、JKTRYJ、JKLHYJ |
1 |
10~400 |
3 |
25~400 |
|
JKLYJ/Q、JKLHYJ/Q |
1 |
10~400 |
JKLGYJ |
1 |
50/8~240/30 |
Product performance indicators
Conductor DC resistance
Nominal cross-section/ |
Maximum Conductor Resistance at 20°C/(Ω/km) |
|||
copper |
Soft copper |
aluminium |
Aluminum alloy |
|
25 |
0.749 |
0.727 |
1.200 |
1.393 |
35 |
0.540 |
0.524 |
0.868 |
1.007 |
50 |
0.399 |
0.387 |
0.641 |
0.744 |
70 |
0.276 |
0.268 |
0.443 |
0.514 |
95 |
0.199 |
0.193 |
0.320 |
0.371 |
120 |
0.158 |
0.153 |
0.253 |
0.294 |
150 |
0.128 |
/ |
0.206 |
0.239 |
185 |
0.1021 |
/ |
0.164 |
0.190 |
240 |
0.0777 |
/ |
0.125 |
0.145 |
300 |
0.0619 |
/ |
0.100 |
0.116 |
400 |
0.0484 |
/ |
0.0778 |
0.0904 |
Cable tearing force
Nominal section mm2 |
Single-core cable breaking force/N |
||
Hard copper |
aluminium |
Aluminum alloy |
|
10 |
3471 |
1650 |
2514 |
16 |
5486 |
2517 |
4022 |
25 |
8465 |
3762 |
6284 |
35 |
11731 |
5177 |
8800 |
50 |
16502 |
7011 |
12569 |
70 |
23461 |
10354 |
17596 |
95 |
31759 |
13727 |
23880 |
120 |
39911 |
17339 |
30164 |
150 |
49505 |
21033 |
37706 |
185 |
61846 |
26732 |
46503 |
240 |
79823 |
34679 |
60329 |
300 |
99788 |
43349 |
75411 |
400 |
133040 |
55707 |
100548 |
AC voltage test
Rated voltage U/kV |
10 |
|
Ordinary insulating structure |
Lightweight and thin insulated structure |
|
Test voltage/kV |
18 |
12 |
Duration/min |
1 |
|
Performance requirements: |
No breakdown |